In order to manage activation of heating or cooling within location, use predefined virtual multi-value switch Mode.

Image Modified

Image Modified
Image Modified
Image Modified
WinterSummerSpring, AutumnSpring / Autumn
  1. To adjust Mode switch to show only modes that are relevant for specific location, use Service Settings of Mode multi-value switch.
  2. In Service Settings, open DEVICE tab and turn on/off specific modes.

...

  • Temperature hysteresis controller
  • Temperature PID controller

Partial support for Mode is also in:

  • Equithermic regulation
  • Blinds adjustment according to sun

...

  • HOT (increasing temperature when output actuator is open) or
  • COLD (decreasing temperature if output actuator is open)
  • DYNAMIC (output actuator is controlling system that can produce both HOT and COLD)

Table below shows behaviour of hysteresis and PID smart rules based on type of Medium and value of Mode switch:

Output actuator is turned on

Medium:
HOT
Medium:
COLD
Heating
Mode

(tick) Hysteresis controller enabled
(tick) PID controller enabled

Output actuator turns (tick)ON when
desired temperature is higher than actual temperature

(error) Hysteresis controller disabled

(error) PID controller disabled

Output actuator is held in (error)OFF state
regardless of temperature

Cooling
Mode
(error) Hysteresis controller disabled
(error) PID controller disabled

Output actuator is held in (error)OFF state
regardless of temperature

(tick) Hysteresis controller enabled
(tick) PID controller enabled

Output actuator is turned on when
desired temperature is lower than actual temperature

Heating
& Cooling
Mode
(tick) Hysteresis controller enabled
(tick) PID controller enabled

Output actuator is turned on when
desired temperature is higher than actual temperature

(tick) Hysteresis controller enabled
(tick) PID controller enabled

Output actuator is turned on when
desired temperature is lower than actual temperature

Off
(No heating,
no cooling)
(error) Hysteresis controller disabled
(error) PID controller disabled

Output actuator is held in (error)OFF state
regardless of temperature

(error) Hysteresis controller disabled

(error) PID controller disabled

Output actuator is held in (error)OFF state
regardless of temperature

...



Filter by label (Content by label)