Heating modeCooling mode
Inputs
  • Outdoor temperature
  • Temperatures from zones
  • Outdoor temperature
  • Temperatures from zones
  • Humidity from zones
Output
  • Set point of virtual thermostat for primary circuit
- Set point of virtual thermostat for primary circuit
Limits
  • Minimal / Maximal set point
  • Minimal / Maximal set point
  • Dew point limit (Early warning)
    Calculates minimal set point temperature based on highest relative humidity from all linked zone thermostats
PID correction(error)(error)


Info

For more information about cooling / heating modes, see Heating and Cooling modes.

Example scenario for zone hydronic heating

...

with equitherm regulation

Image Added

Example scenario for zone hydronic cooling with equitherm regulation

Image Added

How final set point is calculated

Equitherm curve returns temperature of flow water based on outdoor temperature. Angle of the curve, parallel shift, temperature limits and adjustments based on data from thermostats are affecting the final results.

Angle

For floor heating systems, values between 0.2 and 0.8 are commonly used. Lower values are more suitable for high quality insulation.

Outdoor temperature
Slope:-20ºC-15ºC-10ºC-5ºC0ºC5ºC10ºC15ºC20ºC
0.2333232302927242220
0.4424038363330272420
0.6504845413733292520
0.8595652474237312620
1.0656157534740342720
1.2746964585244372820
1.5827670645850403020
1.75908477716354433220
2.0909084777060473420
2.25909088827565523620
2.5909090878070563820
2.75909090908473573820
3.0909090908677614120

Parallel shift

Ratio


Filter by label (Content by label)
showLabelsfalse
max5
spacescom.atlassian.confluence.content.render.xhtml.model.resource.identifiers.SpaceResourceIdentifier@1422e
showSpacefalse
sortmodified
reversetrue
typepage
cqllabel in ("equithermic","cooling","pid","heating") and type = "page" and space = "SUP"
labelspid equithermic heating cooling

...