doc_tap_Equithermic_mode;

CoolM;

Heating modeCooling modedoc_tap_HeatM;doc_tap_
Inputs
  • Outdoor temperature
  • Temperatures from zones
  • Outdoor temperature
  • Temperatures from zones
  • Humidity from zones
CoolllM;
doc_tap_Inp;

doc_tap_OutTemp;

doc_tap_OutTemHu;

Output
  • Set point of virtual thermostat for primary circuit
  • Set point of virtual thermostat for primary circuit
doc_tap_Ootp;

doc_tap_Setcirc;

doc_tap_Setvirtualcirc;

LimitsMinimal / Maximal set point

  • Minimal / Maximal set point
  • Dew point limit (Early warning)
    Calculates minimal set point temperature based on highest relative humidity from all linked zone thermostats
doc_tap_Lim;

doc_tap_MinMax;

doc_tap_

MinMaxDewCal;
PID correction(error)(error)

MinMaxDewCalTher;

doc_tap_PIDc; doc_tap_(XXXX);doc_tap_(XXX);


Info

For more information about cooling / heating modes, see Heating and Cooling modes.

doc_tap_moreInnfo;

How final set point is calculated

doc_tap_HowFinal;

...

doc_tap_EqCurveReturn;

Angle

doc_tap_Angleee;

...

For floor heating systems, values between 0.2 and 0.8 are commonly used. Lower values are more suitable for high quality insulation.

...

doc_tap_FloorTableCurve;

...

doc_tap_
OutTemp
OuTem;
doc_tap_Angle
:
;-20ºC-15ºC-10ºC-5ºC0ºC5ºC10ºC15ºC20ºC
doc_tap_Angle ;
0.2333232302927242220
0.4424038363330272420
0.6504845413733292520
0.8595652474237312620
1.0656157534740342720
1.2746964585244372820
1.5827670645850403020
1.75908477716354433220
2.0909084777060473420
2.25909088827565523620
2.5909090878070563820
2.75909090908473573820
3.0909090908677614120

E.g. if outdoor temperature is 0ºC and angle of equithermic curve is 0.6, resulting set point temperature is 37ºC.

doc_tap_outdoor_37ºC;

...

doc_tap_Parallel_shift;

...

Increases or decreases the curve by defined value.

...

doc_tap_Increases_41ºC;

Adjustments based on data from thermostats

doc_tap_Adjustments_ther;

...

doc_tap_zone_term_ew;

...


doc_tap_
Heatm
Heatmmm;doc_tap_Coolm;
Set point from zonesEquithermic curve will be shifted up if highest set point of zone thermostats is more than 22ºC
Equithermic curve will be shifted down if lowest set point of zone thermostats is less than 22ºC
doc_tap_fZones;doc_tap_shiftup22;doc_tap_shiftdown22;
ResultResulting set point = Set point based on angle and parallel shift + Ratio * (highest zone setpoint - 22)Resulting set point = Set point based on angle and parallel shift + Ratio * (lowest zone setpoint - 22)
doc_tap_Res;doc_tap_setphig22;doc_tap_setplow22;
Dew point limit--Resulting set point can not be less than dew point temperature calculated from highest relative humidity in zones
doc_tap_Dewplim;doc_tap_n;doc_tap_setpzones;

Example scenario for zone hydronic heating with equitherm regulation

doc_tap_Ex_hyeating_eq;

...

doc_tap_Ex_cooling_eq;