Equitherm curve returns temperature of flow water based on outdoor temperature. Angle of the curve, parallel shift, temperature limits and adjustments based on data from thermostats are affecting the final results.
doc_tap_EqCurveReturn;
Angle
doc_tap_Angleee;
...
Table below shows resulting set point temperature based on outdoor temperature and angle of the curve:
doc_tap_FloorTableCurve;
Outdoor temperature | |||||||||
---|---|---|---|---|---|---|---|---|---|
doc_tap_OuTem; | |||||||||
doc_tap_Angle:; | -20ºC | -15ºC | -10ºC | -5ºC | 0ºC | 5ºC | 10ºC | 15ºC | 20ºCdoc_tap_Angle; |
0.2 | 33 | 32 | 32 | 30 | 29 | 27 | 24 | 22 | 20 |
0.4 | 42 | 40 | 38 | 36 | 33 | 30 | 27 | 24 | 20 |
0.6 | 50 | 48 | 45 | 41 | 37 | 33 | 29 | 25 | 20 |
0.8 | 59 | 56 | 52 | 47 | 42 | 37 | 31 | 26 | 20 |
1.0 | 65 | 61 | 57 | 53 | 47 | 40 | 34 | 27 | 20 |
1.2 | 74 | 69 | 64 | 58 | 52 | 44 | 37 | 28 | 20 |
1.5 | 82 | 76 | 70 | 64 | 58 | 50 | 40 | 30 | 20 |
1.75 | 90 | 84 | 77 | 71 | 63 | 54 | 43 | 32 | 20 |
2.0 | 90 | 90 | 84 | 77 | 70 | 60 | 47 | 34 | 20 |
2.25 | 90 | 90 | 88 | 82 | 75 | 65 | 52 | 36 | 20 |
2.5 | 90 | 90 | 90 | 87 | 80 | 70 | 56 | 38 | 20 |
2.75 | 90 | 90 | 90 | 90 | 84 | 73 | 57 | 38 | 20 |
3.0 | 90 | 90 | 90 | 90 | 86 | 77 | 61 | 41 | 20 |
...
doc_tap_outdoor_37ºC;
Parallel shift
doc_tap_Parallel_shift;
...
Increases or decreases the curve by defined value.
...
doc_tap_Increases_41ºC;
Adjustments based on data from thermostats
doc_tap_Adjustments_ther;
All zone termostats that are linked to equithermic smart rule are affecting the final result.
doc_tap_zone_term_ew;
doc_tap_ |
---|
Heatmmm; | doc_tap_Coolm; |
---|
doc_tap_fZones; | doc_tap_shiftup22; | doc_tap_shiftdown22; |
---|
doc_tap_Res; | doc_tap_setphig22; | doc_tap_setplow22; |
---|
doc_tap_Dewplim; | doc_tap_n; | doc_tap_setpzones; |
---|
...
doc_tap_Ex_hyeating_eq;
...