Heating modeCooling mode

doc_tap_Heatmmm;doc_tap_Coolm;
Set point from zones
Equithermic curve will be shifted up if highest set point of zone thermostats is more than 22ºCEquithermic curve will be shifted down if lowest set point of zone thermostats is less than 22ºC
doc_tap_fZones;doc_tap_shiftup22;doc_tap_shiftdown22;
Result
Resulting set point = Set point based on angle and parallel shift + Ratio * (highest zone setpoint - 22)Resulting set point = Set point based on angle and parallel shift + Ratio * (lowest zone setpoint - 22)
doc_tap_Res;doc_tap_setphig22;doc_tap_setplow22;
Dew point limit--Resulting set point can not be less than dew point temperature calculated from highest relative humidity in zones
doc_tap_Dewplim;doc_tap_n;doc_tap_setpzones;

Example scenario for zone hydronic heating with equitherm regulation

doc_tap_Ex_hyeating_eq;

...