Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

doc_tap_exlevel;

Inputs:

  • Reed contact for min level (Variable name: St)
  • Reed contact for max level (Variable name: St1)

Output:

  • Digital output for control of valve or pump (Name: Valve)
  • doc_tap_InpOutp;

    Configuring Equation smart rule


    doc_tap_ConfEqua;

    Info

    Equation smart rule has internal variable called LastState. This variable returns TRUE or FALSE based on last result of evaluation of this smart rule.

    doc_tap_LastStateTrueFalse;

    Equation

    (LastState AND !St1) OR (!LastState AND !St)

    Action

    If result is TRUE: Valve ... Turn On

    If result is FALSE: Valve ... Turn Off

    Duration

    Minimum duration ... 0:05:00 minutes

    doc_tap_EqActDur;