doc_tap_desiredTemperature2;
doc_tap_showconfiguration3;
doc_tap_Ppons;
doc_tap_defined_pipe;
Thermostat doc_tap_Thee; |
---|
doc_tap_Thee; |
doc_tap_BoilerABC;
Boiler A | Boiler B | Boiler C |
---|---|---|
doc_tap_virtualAnalogOut;
Overall Output |
---|
doc_tap_OvOoot; |
doc_tap_BasicConf;
doc_tap_SmartRuleTempPID;
doc_tap_InDe; | doc_tap_SmRu; | doc_tap_OuDe; |
---|---|---|
Thermostat | → PID Controller → P = 2 | Overall Output |
doc_tap_The; | doc_tap_PID0; | doc_tap_OOu; |
doc_tap_Based_BoilerC;
Input device • Overall Output | → Smart Rule → • Equation | Output device • Boiler |
---|---|---|
doc_tap_1IDOO; | doc_tap_1SRE; | doc_tap_1ODB; |
<1% | -- | -- |
doc_tap_01; | doc_tap_001; | |
>1% | Equation: Minimum duration: 5min | TRUE: Turn on Boiler A FALSE: Turn off Boiler A |
doc_tap_1Eq001; | doc_tap_1TrFaBoA; | |
>45% | Equation: | TRUE: Turn on Boiler B FALSE: Turn off Boiler B |
doc_tap_1Eq045; | doc_tap_1TrFaBoB; | |
>90% | Equation: If Overall Output > 0.90 Minimum duration: 5min | TRUE: Turn on Boiler C |
doc_tap_1Eq090; | doc_tap_1TrFaBoC; |
doc_tap_CyclingBo;
doc_tap_boilersextracon;
doc_tap_BoilerPrior;
doc_tap_States_BoCAB;
doc_tap_SequencerABC;
Input device | → Smart Rule → | Output device |
---|---|---|
doc_tap_InnDe; | doc_tap_SmmRu; | doc_tap_OuuDe; |
Virtual push button to start the sequencer | Sequencer Step 1: Priority A (duration 18 hours) Step 2: Priority B (duration 18 hours) Step 3: Priority C (duration 18 hours) Rotate sequence | Boiler Priority |
doc_tap_Virtual_Push_butt; | doc_tap_SeqABC; doc_tap_Rotseq; | doc_tap_BoPri; |
doc_tap_smartrulesA;
Input device • Overall Output | → Smart Rule → • Equation | Output device • Boiler | Limiting Condition |
---|---|---|---|
doc_tap_2IDOO; | doc_tap_2SRE; | doc_tap_2ODB; | doc_tap_2LCond; |
<1% | -- | -- | |
doc_tap_02; | doc_tap_002; | ||
>1% | Equation: If Overall Output > 0.01 | TRUE: Turn on Boiler A FALSE: Turn off Boiler A | Type: Multi-Value Switch Smart Rule will only work if... • Boiler Priority is set to Priority A |
doc_tap_2Eq01; | doc_tap_2TrFaBoA; | doc_tap_2MultiPriorA; | |
>45% | Equation: If Overall Output > 0.45 | TRUE: Turn on Boiler B FALSE: Turn off Boiler B | Type: Multi-Value Switch Smart Rule will only work if... • Boiler Priority is set to Priority A |
doc_tap_2Eq45; | doc_tap_2TrFaBoB | doc_tap_2MultiPriorAA; | |
>90% | Equation: If Overall Output > 0.90 | TRUE: Turn on Boiler C | Type: Multi-Value Switch Smart Rule will only work if... • Boiler Priority is set to Priority A |
doc_tap_2Eq90; | doc_tap_2TrFaBoC | doc_tap_2MultiPriorAAA; |
doc_tap_SimilarLimitingBC;
Input device • Overall Output | → Smart Rule → • Equation | Output device • Boiler | Limiting Condition |
---|---|---|---|
doc_tap_3IDOO; | doc_tap_3SRE; | doc_tap_3ODB; | doc_tap_3LCond; |
<1% | -- | -- | |
doc_tap_03; | doc_tap_003; | ||
>1% | Equation: If Overall Output > 0.01 | TRUE: Turn on Boiler B FALSE: Turn off Boiler B | Type: Multi-Value Switch Smart Rule will only work if... • Boiler Priority is set to Priority B |
doc_tap_3Eq01; | doc_tap_3TrFaBoB | doc_tap_3MultiPriorB; | |
>45% | Equation: If Overall Output > 0.45 | TRUE: Turn on Boiler C FALSE: Turn off Boiler C | Type: Multi-Value Switch Smart Rule will only work if... • Boiler Priority is set to Priority B |
doc_tap_3Eq45; | doc_tap_3TrFaBoC | doc_tap_3MultiPriorBB; | |
>90% | Equation: If Overall Output > 0.90 | TRUE: Turn on Boiler A | Type: Multi-Value Switch Smart Rule will only work if... • Boiler Priority is set to Priority B |
doc_tap_3Eq90; | doc_tap_3TrFaBoA; | doc_tap_3MultiPriorBBB; |
Input device • Overall Output | → Smart Rule → • Equation | Output device • Boiler | Limiting Condition |
---|---|---|---|
doc_tap_4IDOO; | doc_tap_4SRE; | doc_tap_4ODB; | doc_tap_4LCond; |
<1% | -- | -- | |
doc_tap_04; | doc_tap_004; | ||
>1% | Equation: If Overall Output > 0.01 | TRUE: Turn on Boiler C FALSE: Turn off Boiler C | Type: Multi-Value Switch Smart Rule will only work if... • Boiler Priority is set to Priority C |
doc_tap_4Eq01; | doc_tap_4TrFaBoC | doc_tap_4MultiPriorC; | |
>45% | Equation: If Overall Output > 0.45 | TRUE: Turn on Boiler A FALSE: Turn off Boiler A | Type: Multi-Value Switch Smart Rule will only work if... • Boiler Priority is set to Priority C |
doc_tap_4Eq45; | doc_tap_4TrFaBoA; | doc_tap_4MultiPriorCC; | |
>90% | Equation: If Overall Output > 0.90 | TRUE: Turn on Boiler B | Type: Multi-Value Switch Smart Rule will only work if... • Boiler Priority is set to Priority C |
doc_tap_4Eq90; | doc_tap_4TrFaBoB | doc_tap_4MultiPriorCCC; |