Residential split units
doc_tap_Res_s_un;
Compatible with split units supporting Daikin Online Controller. Search for this logo: doc_tap_TCP_logo; |
VRV
doc_tap_VRV_VRV;
RTD-NET Modbus gateway needs to be used for indoor units. Retail price is 278 Euro. Here is documentation.
EKMBDXA Modbus gateway for outdoor unit supports up to 64 indoor units. Integrated control system for seamless connection between Split, Sky Air, VRV, chilers, AHU and BMS systems. Communication via Modbus RS485 protocol.
doc_tap_rtd_ek_proto;
Defining Daikin interface in TapHome
doc_tap_Def_D_Int;
Open Settings → Hardware → TapHome Bus → Terminals and disable one BUS terminal so that you can use it for communication with Daikin.
In Settings → Hardware → Add new interface → Daikin AC
doc_tap_sett_dai_AC;
Add split units with proper address.
doc_tap_add_adres;